Hotel Room Control|& Energy Saving

From in-room RCU to group energy management — better UX, lower OPEX

Boutique hotel guest rooms have to strike a balance between two goals: comfort the guest never has to think about, and energy the operator can actually control. ACEMATIC’s in-room solution uses KNX as the control bus, BLE for key-card and phone identity together with portable sensing, and a room control unit (RCU) that switches automatically between check-in, sleep, cleaning and check-out states.

Guest Room Control Architecture

Each room is anchored by one room control unit as its local core, aggregating the door lock, key-card power, thermostat, lighting, curtains and service calls, and reporting status to the hotel management side in real time. In a typical configuration a single-occupancy room carries roughly 12–20 KNX bus terminals, while a suite multiplies this with its zoning complexity.

  • Power and identity: card-in power is tied to the occupied / unoccupied state, so removing the card drops the room into an energy-saving mode.
  • Climate strategy: driven by occupancy and time of day, with a comfort band (for example 22–24°C) and an unoccupied offset (for example +3°C).
  • Lighting and shading: a soft entry ramp-up, low-level night guide light, and daytime shading that tracks the sun angle to reduce cooling load.

Energy-Saving Strategy and Benchmarks

Saving energy is not about switching lights off; it is about supplying only what is needed. The following ranges are typical and shift with climate and operating intensity:

Measure Target Typical saving Notes
Occupancy-sensed dimming Lighting ~25%–40% Most visible in public areas / corridors
Unoccupied climate offset Air conditioning ~15%–30% Strongly climate dependent
Shading linkage Cooling load ~10%–20% Higher in west-facing rooms
Card-in power Standby draw 60%+ standby cut Eliminates lights left on

Operational tip: start with the three low-cost measures — occupancy-sensed dimming, card-in power and the unoccupied climate offset — then phase in shading linkage and the energy dashboard. Rolling it out in stages keeps troubleshooting manageable and brings the payback forward.

Guest Experience and Operational Integration

Room control does more than save energy; it also carries service. Door status, Do-Not-Disturb and cleaning requests, and SOS calls should all feed into the hotel service system and stay in sync across the in-room panel and the staff terminal. A typical configuration can support:

  • An automatic welcome scene on check-in, with lighting, AC and curtains already in position;
  • A one-touch sleep mode that silences the room and softens public-area cues;
  • Automatic cleaning mode on check-out, cutting housekeeping wait time;
  • A maintenance view that flags a stuck curtain or a failed lamp before the guest ever notices.

Deployment and Acceptance Notes

Getting the room right is mostly discipline at commissioning, not heroics on site.

  • Addressing and BOM: plan KNX group addresses in ETS before devices arrive, and lock the bill of materials to the electrical drawings to avoid field surprises.
  • Scene acceptance: walk every scene (check-in, sleep, away, cleaning, SOS) on real hardware, not just in the config tool, and sign off per room.
  • PMS linkage: where the property management system supports it, map room status to the RCU so that housekeeping, front desk and engineering share one source of truth.
  • Phased rollout: retrofit floor by floor where the building is occupied, keeping one reference room as the template for the rest.

The best room control is the kind a guest never notices — they simply find the right light, the right temperature and the right quiet, every time they walk in.